完整技术指标
Maximum voltage between any Terminal and Earth Ground
· AC:1000 V
· DC:1500 V
· Batteries:2 AA IEC LR6 alkaline
· Display:Dual display with backlight
· Automatic Power Off:20 minutes
精度
· Temperature Coefficients
– Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C
AC Current: Jaw
· Range:999.9 A
· Resolution:0.1 A
· Accuracy:2 % + 5 digits (10 Hz to 100 Hz)
· :2.5 % + 5 digits (100 Hz to 500 Hz)
· Crest Factor (50/60 Hz):2.5 @600.0 A
· :3.0 @500.0 A
· :1.42 @999.9 A
· :Add 2 % for C.F. >2
AC Current: Flexible Current Probe
· Range:999.9 A
· :2500 A
· Resolution:0.1 A (≤999.9 A)
· :1 A (≤2500 A)
· Accuracy:3 % RD + 5 digits (10 Hz to 500 Hz)
· Crest Factor (50/60Hz):2.5 @1400 A
· :3.0 @1100 A
· :1.42@2500 A
· :Add 2 % for C.F. >2
Position Sensitivity
· Distance from Optimum i2500-10 Flex:i2500-18 Flex;Error
· A
– 0.5 in (12.7 mm)
– 1.4 in (35.6 mm)
– ±0.5 %
· B
– 0.8 in (20.3 mm)
– 2.0 in (50.8 mm)
– ±1.0 %
· C
– 1.4 in (35.6 mm)
– 2.5 in (63.5 mm)
– ±2.0 %
DC Current
· Range:999.9 A
· Resolution:0.1 A
· Accuracy:2 % RD + 5 digits [1]
·
– [1] When using the ZERO (B) function to compensate for offsets.
AC Voltage
· Range:600.0 V
· :1000 V
· Resolution:0.1 V (≤600.0 V)
· :1 V (≤1000 V)
· Accuracy:1 % RD + 5 digits (20 Hz to 500 Hz)
DC Voltage
· Range:600.0 V
· :1500 V
· Resolution:0.1 V (≤600.0 V)
· :1 V (≤1500 V)
· Accuracy:1 % RD + 5 digits
mV dc
· Range:500.0 mV
· Resolution:0.1 mV
· Accuracy:1 % RD + 5 digits
Amps Frequency: Jaw
· Range:5.0 Hz to 500.0 Hz
· Resolution:0.1 Hz
· Accuracy:0.5 % RD + 5 digits
· Trigger Level:5 Hz to 10 Hz, ≥10 A
· :10 Hz to 100 Hz, ≥5 A
· :100 Hz to 500 Hz, ≥10 A
Amps Frequency: Flexible Current Probe
· Range:5.0 Hz to 500.0 Hz
· Resolution:0.1 Hz
· Accuracy:0.5 % RD + 5 digits
· Trigger Level:5 Hz to 20 Hz, ≥25 A
· :20 Hz to 100 Hz, ≥20 A
· :100 Hz to 500 Hz, ≥25 A
Voltage Frequency
· Range:5.0 Hz to 500.0 Hz
· Resolution:0.1 Hz
· Accuracy:0.5 % RD + 5 digits
· Trigger Level:5 Hz to 20 Hz, ≥5 V
· :20 Hz to 100 Hz, ≥5 V
· :100 Hz to 500 Hz, ≥10 V
DC Power
· Range:600.0 kVA (600.0 V dc range)
· :1500 kVA (1500 V dc range)
· Resolution:0.1 kVA
· :1 kVA
· Accuracy:2 % RD + 2.0 kVA
· :2 % RD + 20 kVA
Resistance
· Range:600.0 Ω
· :6000 Ω
· :60.00 kΩ
· Resolution:0.1 Ω (≤600.0 Ω)
· :1 Ω (≤6000 Ω)
· :0.01 kΩ (≤60.00 kΩ)
· Accuracy:1 % RD + 5 digits
Capacitance
· Range:100.0 μF
· :1000 μF
· Resolution:0.1 μF (≤100.0 μF)
· :1 μF (≤1000 μF)
· Accuracy:1 % RD + 5 digits
· Inrush Trigger Level:5 A
Mechanical
· Size (L x W x H):281 mm x 84 mm x 49 mm
· Weight (with batteries):520 g
· Jaw Opening:34 mm
· Flexible Current Probe Diameter:7.5 mm
Flexible Current Probe Cable Length
· (head to electronics connector):1.8 m
环境条件
· Operating Temperature:-10 °C to 50 °C
· Storage Temperature:-40 °C to 60 °C
· Operating Humidity:Non condensing ( < 10°C)
· :≤90 % RH (at 10 °C to 30 °C)
· :≤75 % RH (at 30 °C to 40 °C)
· :≤45 % RH (at 40 °C to 50 °C)
· Operating Altitude:2000 m
· Storage Altitude:12 000 m
· Ingress Protection (IP) Rating:IEC 60529: IP54 non-operating
Electromagnetic Compatibility (EMC)
· International
– IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2 CISPR 11: Group 1, Class A
·
– Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for t